Protection Type to
IEC or EN Standards

Basic Principle
Schematic
Principal applications
(d) Flameproof       Enclosure
      IEC 60079-1
      EN 50 018
Parts which can ignite an explosive atmosphere are placed in an enclosure which will withstand the pressure and prevent the explosion being transmitted to the atmosphere around the enclosure
Switchgear and switching installations, control and display units, transformers, motors, heating devices, control boards
(all types of items producing ignitable arcs
in normal operation)
(e) Increased safety
      IEC 60079-7
      EN 50 019
Additional measures are taken to achieve a higher level of safety, avoiding the risk of impermissibly high temperatures, the occurrence of sparks or arcs internally
Terminal and connection boxes, control boxes containing installed components protected by another Ex protection method, squirrel cage motors and light fittings
(i) Intrinsic safety
     IEC 60079-11
     EN 50 020
Equipment within the hazardous area contains only intrinsically safe (I.S.) circuits. A circuit is I.S. if no sparks or thermal effects occur under established test conditions which could lead to the ignition of an explosive atmosphere
Measurement, control and communication equipment, sensors and actuators
(low electric values)
(m) Encapsulation
      IEC 60079-18
      EN 50 028
Equipment which could ignite an explosive atmosphere is embedded in a casting compound
Switchgear for low powers, control gear, indicating and display equipment or sensors
(n) Protection
      IEC 60079-15
      EN 50 021
Equipment incapable of igniting an explosive atmosphere (in normal and defined abnormal operating conditions)
  All electrical equipment suitable for zone 2
(o) Oil immersion
      IEC 60079-6
      EN 50 015
Equipment immersed in a protective liquid in such a way that an explosive atmosphere above the surface or outside the enclosure cannot be ignited
Transformers (rarely used)
(p) Pressurization
      IEC 60079-3
      EN 50 016
Equipment is placed in an enclosure with a protective gas overpressure relative to the surrounding atmosphere. If necessary the enclosure is permanentlysupplied with protective gas to dilute flammable mixtures
Switching and control cabinets, analysis devices, large motors
(q) Powder Filling
      IEC 60079-5
      EN 50 017
Equipment is fixed in a position and completely surrounded by finely ground solids to prevent ignition of the surrounding explosive atmosphere
Electronic devices