Protection Type to |
Basic Principle
|
Schematic
|
Principal applications
|
| (d) Flameproof Enclosure IEC 60079-1 EN 50 018 |
Parts which can ignite an explosive atmosphere
are placed in an enclosure which will withstand the pressure and prevent
the explosion being transmitted to the atmosphere around the enclosure
|
![]() |
Switchgear and switching
installations, control and display units, transformers, motors, heating
devices, control boards (all types of items producing ignitable arcs in normal operation) |
| (e) Increased safety IEC 60079-7 EN 50 019 |
Additional measures are taken to achieve
a higher level of safety, avoiding the risk of impermissibly high temperatures,
the occurrence of sparks or arcs internally
|
![]() |
Terminal and connection boxes, control boxes containing installed components protected by another Ex protection method, squirrel cage motors and light fittings |
| (i) Intrinsic safety
IEC 60079-11 EN 50 020 |
Equipment within the hazardous area contains
only intrinsically safe (I.S.) circuits. A circuit is I.S. if no sparks
or thermal effects occur under established test conditions which could
lead to the ignition of an explosive atmosphere
|
![]() |
Measurement, control
and communication equipment, sensors and actuators (low electric values) |
| (m) Encapsulation IEC 60079-18 EN 50 028 |
Equipment which could ignite an explosive
atmosphere is embedded in a casting compound
|
![]() |
Switchgear for low powers, control gear, indicating and display equipment or sensors |
| (n) Protection IEC 60079-15 EN 50 021 |
Equipment incapable of igniting an explosive
atmosphere (in normal and defined abnormal operating conditions)
|
All electrical equipment suitable for zone 2 | |
| (o) Oil immersion IEC 60079-6 EN 50 015 |
Equipment immersed in a protective liquid
in such a way that an explosive atmosphere above the surface or outside
the enclosure cannot be ignited
|
![]() |
Transformers (rarely used) |
| (p) Pressurization IEC 60079-3 EN 50 016 |
Equipment is placed in an enclosure with
a protective gas overpressure relative to the surrounding atmosphere.
If necessary the enclosure is permanentlysupplied with protective gas
to dilute flammable mixtures
|
![]() |
Switching and control cabinets, analysis devices, large motors |
| (q) Powder Filling IEC 60079-5 EN 50 017 |
Equipment is fixed in a position and completely
surrounded by finely ground solids to prevent ignition of the surrounding
explosive atmosphere
|
![]() |
Electronic devices |