Raychem 5BTV2-CR trace heating cable Maximize

Raychem 5BTV2-CR trace heating cable

Raychem 5BTV2-CR self regulating electric trace-heating cable, mostly used for frost protection of pipes, tanks or vessels which are not subjected to steam cleaning. Capable of continuous exposure temperatures up to +65°C (150ºF) and intermittent exposure temperature up to +85°C (185ºF).

More details

Add to cart

7 Other products in the same category

The Raychem 5BTV2-CR self-regulating parallel circuit trace-heating cable is mostly used for frost protection of piping, which are not subjected to steam cleaning or organic corrosive environments. It may also be used in a variety of industrial applications for process temperature maintenance up to 65°C (150ºF). When used in hazardous areas the unconditional T6 temperature classification simplifies designs and Raychem 5BTV2-CR can be overlapped at valves or flanges with no risk of overheating. The cut to length capability of Raychem BTV family heat tracing cables simplifies electric heat tracing designs for complex piping systems and installation times are reduced due to state-of-the-art connection kits. The self-regulating principle of Raychem BTV heating cables will ensure that the system runs efficiently, saving energy and thereby operational costs.

Raychem 5BTV2-CR technical details
Area classificationHazardous area, Zone 1, Zone 2 (Gas), Zone 21, Zone 22 (Dust)
Traced surfaced typeCarbon steel, stainless steel, plastic, painted or unpainted
Chemical resistanceMild inorganics solutions
Supply voltage230 Vac
  
ATEX approvalsPTB 09 ATEX 1115 X & Baseefa 06ATEX0183X
ATEX markingsEx II 2 G Ex e II T6 & Ex II 2 D Ex tD A21 IP66 T80°C
 IECEx PTB 09.0056X & IECEx BAS 06.0043X
 Ex II 2 G Ex II T6 & Ex II 2 D tD A21 IP66 T80°C
 DNV Certificate No E-8933 for use on ships and mobile offshore units
Maintain temperature65°C (maximum)
Exposure temperature65°C (power on)
 85°C (intermittent power on – maximum cumulative exposure 1000 hours)
Temperature classificationT6 in accordance with European Standard EN 60079-30-1 5.1.13
Installation temperature-60°C minimum
Bend radius13mm at  20°C
 35mm at -60°c
Raychem 5BTV2-CR physical properties
Thickness5.5mm
Width10.5mm
Weight110 g/metre
Conductors2 x 1.2mm² nickel plated copper
Outer sheathModified polyolefin
Power Output

16 watt per metre at 10°C

Maximum circuit length based on type ‘C’ circuit breakers according to EN 60898:
Electric protection sizeStart-up temperatureMaximum cable length
16A-20°C110 m
  10°C160 m
20A-20°C140 m
  10°C160 m
25A & 32A-20°C160 m

 

 10°C160 m