10FMT2-CT trace heating cable Maximize

10FMT2-CT trace heating cable

Raychem 10FMT2-CT constant wattage parrallel circuit trace heating cables, mostly used mainly for temperature maintenance of pipes, tanks or vessels and equipment in industrial locations. 10 w/m output, 190 to 277 Vac, fluoropolymer outer jacket approved for use in hazardous areas Zone 1, Zone 2, Zone 21(Gas) & Zone 22 (Dust). Can withstand exposure temperatures up to 200°C, power off.

More details

Add to cart

8 Other products in the same category

Raychem 10FMT2-CT constant wattage parallel circuit trace heating cable is mostly used for temperature maintenance of pipe, tanks or vessels which are subjected to steam cleaning. It may also be used in a variety of industrial applications for process temperature maintenance up to 150°C. It may also be used for frost protection of large pipes and applications requiring high temperature exposure capability. Its unique geometry provides excellent flexibility during installation and a PTFE insulation tape layer acts as a shock absorber protecting the heating element from shear stress during flexing. The Raychem 10FMT2-CT is a zone parallel heating cable constructed from a heating element wrapped around two parallel conductors. The distance between the conductor contact points forms the heating zone length. The parallel construction allows Raychem 10FMT2-CT to be cut to length and terminated in the "field" during installation. Raychem 10FMT2-CT offers an economical alternative to our Raychem BTV, QTVR, XTV and KTV self regulating trace heating cables but does require more attention during installation and advanced control and monitoring systems.

Technical details:
Area classificationHazardous area, Zone 1, Zone 2 (Gas), Zone 21, Zone 22 (Dust), Ordinary
Traced surfaced typeCarbon steel, stainless steel, plastic, painted or unpainted
Chemical resistance:Organic corrosive solutions
Supply voltage190..270 Vac
  
ATEX approvalsBaseefa 08ATEX0050X
ATEX markingsEx II 2G Ex e II T* (see schedule)) & Ex II 2D Ex tD A21 IP66
 IECEx  BAS 08.0019X
 Ex e II T* (see schedule) & Ex tD A21 IP66
 Product also approved for use in Kazachstan, Russia and other countries
Maintain temperature150°C (maximum)
Intermittent temperature200°C
Min. installation temperature-40°C minimum
Bend radius25mm
Min. clearance50mm
  
Physical properties
Cable diameter7.5mm
Heating zone length1.5m
Jacket colourwhite
Conductors2 x 1.5mm²
Outer sheathFluoropolymer
Power Output

10 watt per metre

Maximum circuit length based on type ‘C’ circuit breakers according to EN 60898:
Voltage Nominal power W/mMax. power W/m
230Vac1012.7