Raychem C-150-E power connection Maximize

Raychem C-150-E power connection

Raychem C-150-E cold applied low profile connection kit. Designed to connect power 100-254 Vac, to a single Raychem BTV, QTVR, XTV or KTV heat trace heating cable. It can be directly mounted to a pipe and may withstand temperatures ranging from -50°C  to +215°C and is approved by PTB for hazardous area use

More details

5 Other products in the same category

Raychem C-150-E cold applied low profile trace heating connection kit. Designed to connect power 100-254 Vac to a single Raychem BTV, QTVR, XTV or KTV trace heating cable. It can be directly mounted to a pipe and may withstand temperatures ranging from -50°C to +215°C and is approved by PTB  for hazardous area use

The Raychem C-150-E may be used with either the Raychem C-150-PC power cable connector or any suitable standard industrial power cable 3 x 1.5mm² or 3 x 2.5mm² wit stranded copper conductors and outer insulation jacket. The Raychem C-150-E trace heating connection kit is used:

  • where connection of a trace heating cable to a junction box is difficult e.g. through space limitations
  • on instrument lines or loading arms
  • where installation of "under insulation trace heating components is preferred 
  • as a cost effective solution for short lengths of trace heating cable as an alternative to a  Raychem JBS-100 

 

Raychem C-150-E kit includes
1 xsplice housing assembly including sealing grommet and strain relief assembly
1 xcore sealer for trace heating cable
1 xspacer including screw terminal
1 xsealing grommet assembly for power cable
1 xpressure plate/strain relief assembly for power cable
1 xidentification label
1 xRaychem installation instruction booklet
  

 

Raychem C-150-E Atex approval details
Area classificationHazardous area, zone 1, zone 2 (Gas), zone 21, zone 22 (Dust)
ATEX approvalsEx e II PTB 09 ATEX 1068 U
ATEX markings Ex II 2G Ex e II
 Ex II 2D Ex tD A21 IP66
 IECEx PTB 09.0043U
 Ex e II
 Ex tD A21 IP66
 DNV Certificate No E-8933 and E-8934
  
Raychem C-150-E enclosure details
Enclosure materialEngineered polymers, colour BLACK
Ingress protectionIP66
SealSilicone rubber
ScrewsStainless steel
Earth continuity plateSteel, zinc plated and blue chromate
Operating temperature-50°C to +50°C ambient
  
Raychem C-150-E technical specification
Heating cable capabilityBTV-CR, BTV-CT, QTVR, XTV, KTV 
Entries2 x M25 (threaded) 
Installation temperature-50°C minimum
TerminalsScrew type (1 phase, 1 neutral, 1 earth)
Max. conductor size1.5 to 2.5 mm² stranded
Max. operating voltage277 Vac
Max. current ratingdepending on power cable and maximum current used
Weight0.4 kg