Raychem 10QTVR2-CT trace heating cable Maximize

Raychem 10QTVR2-CT trace heating cable

Raychem 10QTVR self regulating electric traceheating cable, mostly used mainly for temperature maintenance of pipes, tanks or vessels which are not subjected to steam cleaning. 38 w/m output, 230V, fluoroplymer outer jacket approved for use in hazardous areas Zone 1, Zone 2, Zone 21 (Gas) & Zone 22 (Dust). Capable of continuous exposure temperatures up to +110°C (150ºF) 

More details

Add to cart

2 Other products in the same category

The 10QTVR2-CT Raychem self-regulating parallel circuit trace-heating cable is mostly used for temperature maintenance of pipe, tanks or vessels which are not subjected to steam cleaning. It may also be used in a variety of industrial applications for process temperature maintenance up to 110°C (150ºF). It may also be used for frost protection of large pipes and applications requiring medium temperature exposure capability. When used in hazardous areas the unconditional T4 temperature classification simplifies designs and 10QTVR2-CT can be overlapped at valves or flanges with no risk of overheating. The cut to length capability of QTVR family heat tracing cables simplifies electric heat tracing designs for complex piping systems and installation times are reduced due to state-of-the-art connection kits. The self-regulating principle of QTVR heating cables will ensure that the system runs efficiently, saving energy and thereby operational costs.

Technical Details:
Area classificationHazardous area, Zone 1, Zone 2 (Gas), Zone 21, Zone 22 (Dust)
Traced surfaced typeCarbon steel, stainless steel, plastic, painted or unpainted
Chemical resistance:Organic corrosive solutions
Supply voltage230 Vac
  
ApprovalsPTB 09 ATEX 1116 X & Baseefa 06ATEX0185X
 Ex II 2 G Ex e II T4 & Ex II 2 D Ex tD A21 IP66 T130°C
 IECEx PTB 09.0057X & IECEx BAS 06.0045X
 Ex II 2 G Ex II T4 & Ex II 2 D tD A21 IP66 T130°C
 DNV Certificate No E-8933 for use on ships and mobile offshore units
Maintain temperature110°C (maximum)
Exposure temperature110°C (power on)
Temperature classificationT4 in accordance with European Standard EN 60079-30-1 5.1.13
Installation temperature-60°C minimum
Bend radius13mm at  20°C
 35mm at -60°c
Physical properties:
Thickness4.5mm
Width11.8mm
Weight126 g/metre
Conductors2 x 1.4mm² nickel plated copper
Outer sheathFluoropolymer
Power Output

38 watt per metre

Maximum circuit length based on type ‘C’ circuit breakers according to EN 60898:
Electric protection sizeStart-up temperatureMaximum cable length
25A-20°C95 m
  10°C115 m
32A-20°C115 m
  10°C115 m
40A-20°C115 m
  10°C115 m