nVent RAYCHEM JBU-100-EP trace heating junction box Maximize

nVent RAYCHEM JBU-100-EP trace heating junction box

nVent RAYCHEM JBU-100-EP modular junction box  with earth plate and stud designed  to connect power to up to three Raychem BTV, QTVR, XTV, KTV or VPL heating cables. It can be directly mounted to a pipe or appropriate surface directly via a mounting bracket and is approved by PTB, FM and CSA for use in hazardous areas

 

More details

16 Other products in the same category

 JBU-100-EP kit is designed to connect power to up to three Raychem BTV, QTVR, XTV, KTV or VPL industrial parallel heating cable. It is approved by PTB, FM and CSA, for use in hazardous locations.

The Raychem JBU-100-L-EP is part of a modular component system, it allows for maximum flexibility and can be either wall or pipe mounted. Innovative CAGE CLAMP® terminals from WAGO provide fast installation and safe, reliable, maintenance-free operation.

The connection glands, insulation kits and mounting brackets need to be purchased separately

nVenr RAYCHEM JBU-100-L-EP  kit includes
1 xjunction box with terminals, earth plate and external earth stud
2 xM25 stopping plugs

 

JBU-100-EP approvals
Area classificationHazardous area, Zone 1, Zone 2 (Gas), Zone 21, Zone 22 (Dust)
ATEX approvalsPTB 09 ATEX 1061 U
ATEX markingsEx II 2G Ex e (e mb) II
 Ex II 2D Ex tD (tD mbD) A21 IP66
 IECEx PTB 09.0039U
 Ex e (e mb) II
 Ex tD (tD mbD) A21 IP66
 CSA – Ex e II T*
 DNV Certificate No E-8933 and E-8934
  
JBU-100-EP enclosure details
Enclosure materialElectrostatic charge-resistant glass filled engineered polymer, colour BLACK
Ingress protectionIP66
SealSilicone rubber
Lid screwsStainless steel
Earth continuity plateSteel, zinc plated and blue chromated
Operating temperature-50°C to +56°C ambient
  
JBU-100-EP technical specification
Heating cable capabilityBTV-CR, BTV-CT, QTVR, XTV, KTV & VPL
Entries4 x M25
Installation temperature-50°C minimum
TerminalsSpring-type (2 phase, 2 neutral, 2 earth)
Max. conductor size10 mm² stranded, 10 mm² solid
Operating voltage480 Vac
Max. continuous current40A heating cable circuit
Weight1.8 kg