Raychem S-150 trace heating splice kit Maximize

Raychem S-150 trace heating splice kit

Raychem S-150 cold applied under insulation low profile splice connector. Designed to connect 2 Raychem BTV, QTVR, XTV or KTV heat trace heating cables. The S150 can be directly mounted to a pipe and may withstand temperatures ranging from -50°C  to +40°C and is certified by PTB, FM and CSA for ATEX hazardous area use.

More details

7 Other products in the same category

Raychem S-150 cold applied under insulation low profile trace heating connection kit. The S-150 trace heating connection kits is designed to connect or splice two Raychem BTV, QTVR, XTV or KTV trace heating cables. It can be directly mounted to a pipe, withstand temperatures ranging from -50°C to +215°C and is approved by PTB and CSA for hazardous area use. 

The unigue design of the Raychem S-150 cold applied under insulation trace heating splice suits the demands of industrial environments with features such as: 

  • low profile housing, for direct installation on pipes or other surfaces
  • rugged housing which is resistant to impact, high temperature and chemical exposure
  • double moisture ingress protection via spring loaded grommet and non-curing silicone free sealant 
  • access to cable connections, through a re-enterable gland grommet
  • no heat source required  

 

Raychem S-150 kit includes
1 xsplice housing assembly including sealing grommet and strain relief assembly
2 xcore sealer for trace heating cable
2 xsealing grommets for trace heating cable
1 xspacer including screw terminals
1 xidentification label
1 xRaychem installation instruction booklet
  

 

Raychem S-150 Atex approval details
Area classificationHazardous area, zone 1, zone 2 (Gas), zone 21, zone 22 (Dust)
ATEX approvalsEx e II PTB 09 ATEX 1068 U
ATEX markings Ex II 2G Ex e II
 Ex II 2D Ex tD A21 IP66
 IECEx PTB 09.0043U
 Ex e II
 Ex tD A21 IP66
 DNV Certificate No E-8933 and E-8934
  
Raychem S-150 enclosure details
Enclosure materialEngineered polymers, colour BLACK
Ingress protectionIP66
SealSilicone rubber
ScrewsStainless steel
Operating temperature-50°C to +50°C ambient
  
Raychem S-150 technical specification
Heating cable capabilityRaychem BTV-CR, BTV-CT, QTVR, XTV, KTV 
Entries2 x trace heating cable
Installation temperature-50°C minimum
TerminalsScrew type (1 phase, 1 neutral, 1 earth)
Max. conductor size2.5 mm² stranded
Operating voltageupto 277 Vac
Max. continuous current40A heating cable circuit for PTB
Weight0.4 kg