Raystat Control-10 thermostat, surface sensing Maximize

Raystat Control-10 thermostat, surface sensing

Raychem Raystat Control-10 thermostat, surface sensing, programmable with alarm relay controller. 25A SPDT

More details

8 Other products in the same category

Trace heating - Raychem Raystat Control-10 thermostat, surface sensing controller for trace heating cables, 25A SPDT. The Raychem Raystat Control-10 thermostat is NOT approved for use in ATEX rated hazardous areas. The Raychem Raystat Control-10 provides temperature control for one Raychem BTV, QTVR, XTV & KTV self regulating trace heating cable or one VPL power limited trace heating cable or one FHT, FMT constant wattage trace heating cable. The Raychem Raystat Control-10 has 25A switching capacity, temperature range 0°C to 150°C and LED indication when trace heating cables are energised (Trace heating ON), current and set point temperature display and temperature sensor is defective (sensor break or short circuit). The Raychem Raystat Control-10 thermostat has a 3m long temperature probe to facilitate pipe mounting. Direct connection of Raychem trace heating cable is possible to the Raystat Control-10 (Raychem connection kits ordered separately) Benefits include, energy saving trace heating running cost, easy installation and commissioning, low cost installation.

Raychem Raystat Control-10 technical details
Area classificationOrdinary area, outdoors
ATEX approvalsNone
ATEX markingsNone
  
Raychem Raystat Control-10 enclosure details
MaterialGrey polycarbonate base, transparent lid, 4 captive screws
Ingress protectionIP65 according to EN 60529
Temperature adjustmentInside housing
Entries2 x M25, 1 x M20 & 1 x M16
Operating temperature-20°C to +40°C ambient
  
Raychem Raystat Control-10 switching
TypeSingle pole change over volt free contacts (SPDT)
Supply voltage230V 50/60Hz
Rating25A at 250 Vac
Alarm relay2A at  250 Vac (volt free)
  
Raychem Raystat Control-10 temperature sensing
Type3 wire Pt-100 according to IEC Class B
Cable length3 metres
Exposure temperature200°C
  
  
Raychem Raystat Control-10 parameter settings
Maintain set point0°C to +150°C
Hysteresis 1 K to 5 K
Low temperature alarm-40°C to +148°C
High temperature alarm2°C to +150°C or switched OFF
Heater operation if sensor errorON or OFF
Voltage free operationYes or No
  
Raystat Control-10 parameters may be programmed without power supply (internal battery) and stores in non volatile battery
  
Raychem Raystat Control-10 connection terminals
Supply:3 terminals for upto 0.75 mm² to 4 mm² conductors
Pt 100 connection4 terminals for upto 0.75 mm² to 2.5 mm² conductors
Control relay connection3 terminals for upto 0.75 mm² to 4 mm² conductors
Alarm relay connection3 terminals for upto 0.75 mm² to 2.5 mm² conductors
  
Associated support brackets
Raychem SB-100, SB-101
 
Maximum recommended heating cable length is restricted by the electrical protection sizing or the switching capacity of the Raychem Digitrace Control-10. For more details - download Raychem Control-10