ATX FE series explosion proof fluorescent lights are suitable for use in ATEX rated hazardous area zone 1, zone 2, zone 21 & zone 22, ingress protection rated IP66/67, suitable for wall or ceiling mounting, has an electronic multi-tap ballast, high impact resistance housing, hinged parabolic reflector and vibration resistant lamp holders suitable for G13 fluorescent bi-pin lamps.

  • TECHNICAL DETAILS
    Specification
    EnclosureCorrosion resistant glass fibre reinforced polyester resin
    CoverPolycarbonate
    GasketElastomer
    Ingress protectionIP66/67
    Cable entries3 x M20
    Operating temperature-40°C to +55°C ambient, wind profile for harsh onshore and offshore environments
    Ballast1 x electronic multi-tap dual channel
    Supply voltageV a.c. 110...254 ±10%, 50/60 Hz
    V d.c. 110...254 , 50/60 Hz
    Emergency operationBattery 4 Ah, duration 3 hours (emergency variant only)
    Lamp holderT8 (G13)
    Lamp disconnectPositive safety switch disconnects power to lamps and ballast
    Terminals2 x 5 terminals, 6mm2 solid core, 4mm2 flexible core
    2 x 4 terminals, 6mm2 solid core, 4mm2 flexible core (emergency variant)


    Part numberNumber of lampsPower (W)EntriesECP
    FEB218BUTA (E)2183 X M20
    FEB236BUTA (E)236
    FEB258BUTA (E)258
    FEB218BUTN  (E)2183 x M25
    FEB236BUTN (E)236
    FEB258BUTN (E)258
  • APPROVALS
    Approvals
    ATEX
    GAS Ex II 2GD  Ex de or demb IIC T4 or T5 (*) Gb
    DUST Ex II 2D Ex t IIIC T75°C Db IP66/67
    -40°C ≤ Ta ≤ +55°C
    * in position of lighting downwards with Tamb = +40°C
    IECEx
    Ex de or demb IIC T4 or T5 (*) Gb
    Ex t IIIC T75°C Db IP66/67
    -40°C ≤ Ta ≤ +55°C
    * in position of lighting downwards with Tamb = +40°C
    Other
    GOST, Marine Listed UL 1598A
    Ex Standards
    EN / IEC 60079-0; 60079-1; 60079-7; 6079-18; 61241-0; 61241-1
    Product Standards
    EN / IEC 60598-1; 60598-2-22
    EMC Standards
    EN / IEC 55015; 61547
  • DIMENSIONS
    Dimensions (mm) and Weight (kg) - non emergency
    Power (W)LengthWidthHeightWeight
    187852171455.5
    3613902171457.9
    5816902171459
    Dimensions (mm) and Weight (kg) - emergency variant
    187852171457.3
    3613902171459.6
    58169021714511.6