Product details
Control Station CS-2014: ATEX zone 1 hazardous area approved, explosion proof 2 gang control station with STOP / START double push button and emergency stop. The CS-2014 has 2 x double pole single throw (DPST) contact configuration, current rating of 16 A and a voltage rating of 500 V. The housing is made of plastic material
Control Station CS-2014: Features & Benefits
- robust, impact resistant polyamide enclosure, IP66 (standard)
- suitable for zone 1 hazardous areas
- 1 x "STOP" / "START" double push button
- 2 x 1 NO / 1 NC DPST contact configuration
- 1 x bottom cable entry complete with gland, M20 (standard)
- TECHNICAL DETAILS
SPECIFICATIONS Approved Hazardous area Zone 1 and Zone 21 Rated voltage 500 V a.c. Max. current rating 16 A Rated current with gold contact points 0.4 A Temperature range -20°C to +40°C Rated making / breaking capacity AC-3 AC-15: Ue 250 V / Ie 6 A
AC-15: Ue 500 V / Ie 4A
DC-13: Ue 24 V / Ie 6 A
DC-13: Ue 220V Ie 1 AEX push button 1 x double momentary push button STOP / START
1 x emergency stopContact 2 x NO/NC contact - standard Terminals 2 x 2.5 mm2 - standard Enclosure material polyamide: colour BLACK Gasket material neoprene Temperature classification IP 66 Entries 1 x M20 - standard (2 X M25/M20 max) Manufacturer EATON, CEAG Manufacturer's part number GHG 411 8200 R0016 - APPROVALS
APPROVALS ATEX:
GAS: Ex II 2G Ex ed ib m IIC T6
DUST: Ex II 2D Ex tD A21 IP66 T80°CIECEX:
Ex e II T6, Ex e ib IIC T6, EX ed IIC T6 or Ex ed ib IIC T6 - DIMENSIONS
DIMENSIONS AND WEIGHT Width (mm) 85Height (mm) 125 Depth (mm) 77.5Weight (kg) 0.65