PS-1681 - Wall socket, 16A 500V 4 pole hazardous area - CEAG

PS-1681 Wall socket 16A 500V 4 pole for potential explosive atmopsheres in hazardous area

PS-1681 - Wall socket, 16A 500V 4 pole hazardous area - CEAG


$0.00
$631.33
/ ea
Earn0
reward points

Lead time: 4 weeks


Product details

PS-1681: Wall socket 16A 500V 4 pole for use in hazardous areas zone 1, zone 21, zone 2 and zone 22. motor switching capacity AC-3 to DIN EN 60947-3. High safety standard, steady hold and faultless contacting even under vibration or in aggressive atmospheric conditions

Features & Benefits

  • Robust: glass fibre reinforced polyester enclosure, IP66
  • Contacts: self cleaning lamellar, nickel plated 
  • All pole ON/OFF switching
  • Low insertion force, easy plugging
  • TECHNICAL DETAILS
    SPECIFICATIONS
    ApprovedHazardous area Zone 1 and Zone 21
    Rated voltage480 - 500 V a.c.
    Max. current rating 16 A
    Frequency400 Hz
    Temperature range-20°C to +55°C
    Rated making / breaking capacity AC-3U690 V / Ie 16 A
    Terminals1 x 1.0 - 4.0 mm2
    External back up fuse max.with therm. protection 16 A
    without therm. protection 35 A gL (rated current 16 A set to)
    Enclosure materialglass fibre reinforced polyester: colour BLACK
    Temperature classificationIP 66
    Entries2 x M25. (1 x M25 gland, 1 x M25 plugged)
    ManufacturerEATON, CEAG
    Manufacturer's part numberGHG 511 4407 R0001


  • APPROVALS
    APPROVALS
    ATEX: 
    GAS: Ex II 2G Ex db eb [ia] IIC/IIB +H2 T6
    DUST: Ex II 2D Ex IIIC T80°C Db

    IECEX:
    Ex ed [ia] IIC T6/T5

  • DIMENSIONS
    DIMENSIONS AND WEIGHT

    Width (mm)
    110
    Height (mm)236
    Depth (mm)
    147
    Weight (kg)
    1.3