Product details
nVent RAYCHEM C25-01 connection kit is for terminating all nVent RAYCHEM BSA and BTV-CR polyolefin jacket self-regulating heating cables to a junction box, whilst maintaining electrical insulation of the cable conductors and core. Ordinary (non-hazardous) areas
- TECHNICAL DETAILS
SPECIFICATIONS Approved nVent RAYCHEM heating cables: BSA, BTV-CR self-regulating Type hot applied Thread size M25 x 1.5 Max. exposure temperature (gland) +100°C Min. ambient temperature -20°C Gland material Polyamide: colour BLACK Temperature classification IP 66 Weight (kg) 0.06 C25-01 connection kit contentsM25 x 1.5 polyamide gland 1 Grommet 1 Heat shrink sleeves for core sealing 2 Green/yellow tube 1 * IMPORTANT* The above numbers are for circuit length estimation only. For more detailed information please request nVent RAYCHEM TraceCalc software design. nVent requires the use of a 30 mA residual current device to provide maximum safety and protection from fire. Where design results in higher leakage current, the preferred trip level for adjustable devices is 30 mA above any inherent capacitive leakage characteristic of the heater as specified by the trace heater supplier or alternatively, the next common available trip level for non adjustable devices, with a maximum of 300 mA. All safety aspects need to be proven - APPROVALS
APPROVALS DNV TAE00003ES
When used with BSA, BTV-CRProducts are in compliance with IEC/EN 62395-1:2013 - DOWNLOAD DOCUMENTS