Product details
nVent RAYCHEM C25-100-Metal connection kit is for terminating all nVent RAYCHEM BTV, HTV, KTV, QTVR and XTV self-regulating and VPL power limiting heating cables to a junction box, whilst maintaining electrical insulation of the cable conductors and core. The C25-100-Metal is approved for use in hazardous areas
- TECHNICAL DETAILS
SPECIFICATIONS Approved nVent RAYCHEM heating cables: BTV, HTV. KTV, QTVR and XTV self-regulating; VPL power limiting Type cold applied Thread size M25 x 1.5 Max. exposure temperature (gland) +180°C Min. ambient temperature -60°C Gland material C25-100-Metal: brass
C25-100-Metal-NP: nickel plated brass
C25-100-Metal-SS: stainless steelTemperature classification IP 68 Weight (kg) 0.31 C25-100-Metal connection kit contentsM25 x 1.5 metal gland 1 Locknut 1 Sealing washer 1 (C25-100-Metal variant only) Grommets 2 Core sealer 1 * IMPORTANT* The above numbers are for circuit length estimation only. For more detailed information please request nVent RAYCHEM TraceCalc software design. nVent requires the use of a 30 mA residual current device to provide maximum safety and protection from fire. Where design results in higher leakage current, the preferred trip level for adjustable devices is 30 mA above any inherent capacitive leakage characteristic of the heater as specified by the trace heater supplier or alternatively, the next common available trip level for non adjustable devices, with a maximum of 300 mA. All safety aspects need to be proven - APPROVALS
APPROVALS ATEX: Baseefa 16ATEX0039U
Ex II 2 GD Ex eb IIC GB
Ex tb IIIC DbIECEX: BAS 16.0042U
Ex eb IIC Gb
Ex tb IIIC DbNB. For HTV cable only and C25-100-Metal
The following system certificates are applicable: PTB 21ATEX1003X and IECEX PTB 21.0007XEAC Ex RU C-BE.MЮ62.B.00054/18
1Ex e IIC Gb U
Ex tb IIIC Db U
Ta -60°C...+180°C IP68
ООО "ТexИмпорт" - DOWNLOAD DOCUMENTS