RAYCHEM C25-100-Metal power connection kit, cold applied M25 gland - nVent

nVent Raychem C25-100-Metal connection kit with M25 brass gland

RAYCHEM C25-100-Metal power connection kit, cold applied M25 gland - nVent


$0.00
$65.75
/ ea
Earn0
reward points


Lead time: 3 to 5 days


Product details

nVent RAYCHEM C25-100-Metal connection kit is for terminating all nVent RAYCHEM BTV, HTV, KTV, QTVR and XTV self-regulating and VPL power limiting heating cables to a junction box, whilst maintaining electrical insulation of the cable conductors and core. The C25-100-Metal  is approved for use in hazardous areas 


  • TECHNICAL DETAILS
    SPECIFICATIONS
    ApprovednVent RAYCHEM heating cables: BTV, HTV. KTV, QTVR and XTV self-regulating; VPL power limiting 
    Typecold applied
    Thread sizeM25 x 1.5
    Max. exposure temperature (gland)+180°C
    Min. ambient temperature-60°C
    Gland materialC25-100-Metal: brass
    C25-100-Metal-NP: nickel plated brass
    C25-100-Metal-SS: stainless steel
    Temperature classificationIP 68
    Weight (kg)0.31


    C25-100-Metal connection kit contents
    M25 x 1.5 metal gland1
    Locknut1
    Sealing washer1 (C25-100-Metal variant only)
    Grommets2
    Core sealer1


    * IMPORTANT* The above numbers are for circuit length estimation only. For more detailed information please request nVent RAYCHEM TraceCalc software design. nVent requires the use of a 30 mA residual current device to provide maximum safety and protection from fire. Where design results in higher leakage current, the preferred trip level for adjustable devices is 30 mA above any inherent capacitive leakage characteristic of the heater as specified by the trace heater supplier or alternatively, the next common available trip level for non adjustable devices, with a maximum of 300 mA. All safety aspects need to be proven
  • APPROVALS
    APPROVALS
    ATEX: Baseefa 16ATEX0039U
    Ex II 2 GD Ex eb IIC GB
    Ex tb IIIC Db

    IECEX: BAS 16.0042U
    Ex eb IIC Gb
    Ex tb IIIC Db

    NB. For HTV cable only and C25-100-Metal
    The following system certificates are applicable: PTB 21ATEX1003X and IECEX PTB 21.0007X

    EAC Ex RU C-BE.MЮ62.B.00054/18
    1Ex e IIC Gb U
    Ex tb IIIC Db U
    Ta -60°C...+180°C IP68
    ООО "ТexИмпорт"


  • DOWNLOAD DOCUMENTS