Raychem C25-21 power connection kit, hot applied M25 gland - chemelex®

nVent Raychem C25-21 connection kit

Raychem C25-21 power connection kit, hot applied M25 gland - chemelex®


$0.00
$24.27
/ ea
Earn0
reward points

Lead time: 3 to 5 days


Product details

chemelex® Raychem C25-21 connection kit is for terminating all chemelex® Raychem BTV, KTV, QTVR and XTV self-regulating and VPL power limiting heating cables to a junction box, whilst maintaining electrical insulation of the cable conductors and core. The C25-21 is approved for use in hazardous areas 


Features & Benefits

  • Easy to use and fast to install
  • Versatile: approved for all chemelex® Raychem self-regulating and power limiting heating cables
  • Simplified design in hazardous area, part of system approval
  • Reliable long life: maintenance free, 10 year product warranty available
  • TECHNICAL DETAILS
    SPECIFICATIONS
    Approvedchemelex® Raychem heating cables: BTV, KTV, QTVR and XTV self-regulating; VPL power limiting 
    Typehot applied
    Thread sizeM25 x 1.5
    Max. exposure temperature (gland)+110°C
    Min. ambient temperature-55°C
    Gland materialPolyamide: colour BLACK
    Temperature classificationIP 66
    Weight (kg)0.06


    C25-21 connection kit contents
    M25 x 1.5 polyamide gland1
    Locknut1
    Grommets2
    Heat shrink sleeves for core sealing2
    Green/yellow tube1


    * IMPORTANT* The above numbers are for circuit length estimation only. For more detailed information please request chemelex® Raychem TraceCalc software design. chemelex® requires the use of a 30 mA residual current device to provide maximum safety and protection from fire. Where design results in higher leakage current, the preferred trip level for adjustable devices is 30 mA above any inherent capacitive leakage characteristic of the heater as specified by the trace heater supplier or alternatively, the next common available trip level for non adjustable devices, with a maximum of 300 mA. All safety aspects need to be proven
  • APPROVALS
    APPROVALS
    ATEX: Baseefa 16ATEX0037U
    Ex II 2 G Ex eb IIC GB
    Ex II 2 D Ex tb IIIC Db

    IECEX: BAS 16.0040U
    Ex eb IIC Gb
    Ex tb IIIC Db
    DNV TAE00000TU and TAE 00000TV
    When used with BTV, QTV heating systems: DNV certficate TAE00000TU
    When used with KTV, XTV heating systems: DNV certificate TAE00000TV

    EAC Ex RU C-BE.MЮ62.B.00054/18
    1Ex e IIC Gb X
    Ex tb IIIC Db X
    Ta -55°C...+110°C IP66