Product details

nVent RAYCHEM E-150 end seal kits. Electrostatic charge resistant glass filled engineered polymer enclosure, cold applied without the need for a hot work permit, with low profile for placement under insulation. The E-150 end seal kits terminate one heating cables and are approved for use in hazardous areas with nVent RAYCHEM BTV, KTV, QTVR, XTV and XTVR self-regulating heating cables.

  • Rugged: integral pipe mount stand protects heating cables
  • Simple to design: up to 277 VAC, 40 A
  • Easy to install: re-entrable seal, no hot work permit required
  • Reliable long life: maintenance free, 10 year product warranty available
  • TECHNICAL DETAILS
    SPECIFICATIONS
    ApprovednVent RAYCHEM heating cables: BTV, KTV, QTRV, XTV and XTVR self-regulating
    Rated voltage277 VAC
    Temperature range-55°C to +215°C
    Min. installation temperature-55°C
    Enclosure materialelectrostatic charge resistant glass filled polymer: Colour BLACK
    Sealing grommetsilicone
    Core sealersilicone
    Screws, compression springstainless steel
    Temperature classificationIP 66
    E-150 end seal kit contents
    end seal enclosure 1
    sealing grommet assembly1
    core sealing boot1
    identification label1
    * IMPORTANT* The above numbers are for circuit length estimation only. For more detailed information please request nVent RAYCHEM TraceCalc software design. nVent requires the use of a 30 mA residual current device to provide maximum safety and protection from fire. Where design results in higher leakage current, the preferred trip level for adjustable devices is 30 mA above any inherent capacitive leakage characteristic of the heater as specified by the trace heater supplier or alternatively, the next common available trip level for non adjustable devices, with a maximum of 300 mA. All safety aspects need to be proven


  • APPROVALS
    APPROVALS
    ATEX: DEKRA 20ATEX0011U
    Ex II 2 G Ex eb IIC Gb
    Ex II 2 D Ex tb IIIC Db

    IECEX: IEC DEK 20.0005U
    Ex eb IIC Gb
    Ex tb IIIC Db

    DNV: TAE0000TU and TAE00000TV
    The E-150 approved by DNV for use on ships and mobile offshore units

    EAC Ex: RU C-BE.MЮ62.B00054/18
    Ex e IIC Gb U or Ex tb IIIC Db U
    Ta -55°C...+215°C  IP66
    ООО "ТexИмпорт"
    CCC (1)
    Ex e IIC Gb
    Ex tD A21 IP66

  • DIMENSIONS
    Dimensions and Weight
    Length (mm)
    100
     width (mm)
    57
    depth (mm)
    57
    Weight (kg)
    0.35