Product details
nVent RAYCHEM ETS-05 electronic controller provides accurate control of heating cables for freeze protection and temperature maintenance. The ETS-05 has a LED indicator which indicates the status of the thermostat (powered on/off), the heat tracing cable (powered on/off) and the sensor. In case of sensor failure the thermostat can switch to an on or off state (set by user).
RAYCHEM ETS-05 Features & Benefits
- Precise control: Line sensing
- Adjustable range: 0°C to +199°C (L variants) and 0°C to +499°C (H variants)
- LED indication: LED provide status indication
- Simple to design: direct connection of heating cables possible
- Switching: SPST, 32 A, 230V (110 V a.c. variants available)
- TECHNICAL DETAILS
SPECIFICATIONS Application pipe freeze protection and temperature maintenance Area of Use hazardous area Sensor type surface temperature sensing Temperature range -55°C to 260°C (ETS-05-L2**)
0°C to 499°C (ETS-05-H2**)Maximum sensor lead resistance 20 Ohm Setpoint range 0°C to 199°C (ETS-05-L2**)
0°C to 499°C (ETS-05-H2**)Switch accuracy ± 1 K at 5°C (calibration point) Switching hysteresis ≈ 3°C Adjustable temperature range -40°C to +60°C Electrical Supply voltage 195 - 230 V a.c. +10% 50/60 Hz (ETS-05-*2-**)
195 - 277 V a.c. +3% 50/60 Hz (ETS-05-*2R-**)
110 V a.c. ±10% 50/60 Hz (ETS-05-*1-**)
99 - 132 V a.c. 50/60 Hz (ETS-05-*1R-**)Terminals power supply: 4 x 6 mm²
heating cable: 3 x 6 mm²
sensor: 4 x 1.5 mm²Output relay single pole change over type (SPST) Switching capacity output relay 32 A resistive load Alarm relay 275 V a.c. 3A resistive load ETS-05-**-**-A variants only Circuit breaker max. 32 A (C-type characteristic) Internal power consumption 3 VA LED Indications LED indication - power ON, heat tracing cable OFF: GREEN
- power ON, heat tracing cable ON: YELLOW
- sensor failure: FLASHING RED
Enclosure Material glass fibre reinforced polymer Earthing plate ETS-05-**-EP variants only Ingress protection IP 66 Mounting option On pipe: Support brackets SB-100, SB-101, SB-110, SB-111 and SB-130
Surface: using 4 x M6 fixing holes at 106 mm x 82 mm centresMounting holes 4 x M6 Entries 2 x M25: power / heating cable
1 x M16: sensor cable
1 x M20: alarm relay (ETS-05-**-**-A variants only)Storage temperature -40°C to +50°C Sensor Type PT100 3 wire, 2 m long, flexible (ETS-05-L2**)
PT100 3 wire, 2 m long, stainless steel (ETS-05-H2**)Temperature range -55°C to 260°C (ETS-05-L2**)
0°C to 499°C (ETS-05-H2**) - APPROVALS
APPROVALS ATEX: Baseefa 13ATEX0137
Ex II 2(1) G II 2D
Ex e ia mb (Ga) IIC T5 GB
Ex tb IIIC T100°C Db IP66
Ta -40°C to +60°C Supply = 99-121V (ETS-05-x1-x) or 195-230V (ETS-05-x2-x)IECEX: BAS 13.0071
Ex II 2(1) G II 2D
Ex e ia mb (Ga) IIC T5 GB
Ex tb IIIC T100°C Db IP66
Ta -40°C to +60°C Supply = 99-121V (ETS-05-x1-x) or 195-230V (ETS-05-x2-x)EAC (ETS-05-L2**)
Ex: TC RU C-BE.ИM43.B.01764
1Ex e ia mb [iaGa] IIC T5 Gb X
Ex tb mb IIIC T100°C Db X IP66
Ta -52°C ...+60°C IP66
ООО "ТexИмпорт"EAC (ETS-05-L2**)
Ex: TC RU C-BE.ИM43.B.01764
1Ex e ia mb [iaGa] IIC T5 Gb X
Ex tb mb IIIC T100°C Db X IP66
Ta -60°C ...+60°C IP66
ООО "ТexИмпорт" - DIMENSIONS
DIMENSIONS AND WEIGHT Width 120 mm Height 120 mm (excluding glands) Depth 90 mm Weight 1.4 kg - DOWNLOAD DOCUMENTS