Product details
nVent RAYCHEM IceStop GM2X and GM2XT heating cable is designed to provide snow melting and de-icing for roof or gutter systems.
Features & Benefits
- Self-regulating technology: regulates heat output according to ambient temperature
- Efficient: energy saving
- Simple to design: streamline and simplified design flexible cable, cut to length
- Low installed cost: flexible cable, cut to length on site
- Control: advanced control and monitoring to maximum energy savings
- Reliable: 10 year warranty
- TECHNICAL DETAILS
SPECIFICATIONS Application Roof, gutter snow melting or de-icing Min.nominal power output 36 W/m at 0°C in ice water Maximum circuit length 80 m Circuit beaker type /size Type C / max. 20 A Suitable for standard materials Slate: ✓
Shingle: ✓
Bitumen: ✓
Tar: ✓
Wood: ✓
Metal: ✓
Plastic: ✓Maximum exposure temperature 65°C - continuous Maximum exposure temperature 85°C - intermittent (power on) Braid Tinned copper Braid coverage 80 % Outer jacket material GM2X: Modified Polyolefin
GM2XT: FluoropolymerOuter jacket colour BLACK Minimum bend radius 16 mm Supply voltage 230 VAC Chemical resistance GM2X: Inorganic Solutions
GM2XT: Organic substancesIceStop GM2 cable
(230 VAC)Maximum circuit length (m). Based on start up temperature +12°C 10 A 13 A 16 A 20 A GM2X (XT) 40 50 60 80 *** IMPORTANT *** 30 mA residual current device (RCD) and a circuit breaker (C-type characteristic) required for maximum safety and fire protection. - APPROVALS
APPROVALS Tested and approved VDE, and SEMKO - DIMENSIONS
DIMENSIONS AND WEIGHT Thickness 6.2 mm Width 13.7 mm Weight 0.13 kg/m Conductors 2 x 1.2 mm² nickel plated copper - DOWNLOAD DOCUMENTS