Product details
nVent RAYCHEM Raystat Control-11-DIN line sensing electronic thermostat for operation of self-regulating heating cables for freeze protection and temperature maintenance applications. It is designed for operation with nVent RAYCHEM XL-Trace, FS-C10-2X, FroStop self-regulating trace heating cables.
Features & Benefits
- Easy to read digital display for temperature and alarm
- Full programmable: 8 Parameter settings
- Ease of operation: Easy to use digital display
- Sensor monitors pipe temperature fail safe, heating circuit OFF or ON
- Versatile: DIN rail or panel mountable
- Reliable: 6 year warranty
- TECHNICAL DETAILS
SPECIFICATIONS Application Freeze protection and temperature maintenance nVent RAYCHEM heating cables XL-Trace, FS-C10-2X, FroStop Black Area of Use Ordinary area, IP 30 (Terminals: IP20) Supply voltage 230 V a.c., 50-60 Hz Terminals 2.5 mm², screw type Switching capacity output relay 230 V a.c., 16 A Relay K1: 16 A res., 6 A ind.
K2: 8 A res., 3 A ind.Power consumption max. 5 VA Accuracy ± 1 K, ± 2 digits (0..50°C) Hysteresis ±1 K Ambient temperature range -10°C to +55°C Display and programming Screen type LED: colour RED 1/2" Parameters
P01: Actual sensor temperature
P02: Control setpoint
P03: Switching hysteresis
P04: High control setpoint
P05: Low control setpoint
P06: Fail safe mode
P07: Low temperature alarm
P08: Parameter lock
P09: Access code
°C (display only)
Affects to relay 1, P04 and P05
Affects P02 range (1..5 K)
Range: 0°C ... 63°C
Range: 0°C ... P04
0 = relay OFF at probe fault
1 = relay ON at probe fault
-15°C ... (P02-P03)°C
0 = parameter P03..P07 UNLOCKED
1 = parameter P03..P07 LOCKED
Access code to unlock P08Enclosure Material Acrylonitrile butadiene styrene (ABS) Ingress protection IP20 (in panel IP30) Mounting option mountable DIN rail 35 mm Storage temperature -20°C to +60°C Sensor Type Pt100 3 wire Tip dimensions ⌀ 5 mm; length 20 mm Cable length 10 m (2-wire) Exposure temperature range 0°C to +70°C Accuracy ±1 K *** IMPORTANT ***
All connections between the electrical supply, control panel and self-regulating temperature maintenance cable circuits shall be installed by an approved electrical contractor and protected by MCB (BS EN 60898 type C or D) and RCD (30 mA sensitivity, tripping within 100ms). - APPROVALS
APPROVALS CE, ROHS, VDE, REACH - DIMENSIONS
DIMENSIONS AND WEIGHT Width 51.5 mm Height 87.5 mm Depth 58 mm Weight 0.55 kg - DOWNLOAD DOCUMENTS