Product details
The nVent RAYCHEM SBS trace heating control panel, combines with all XL-Trace, Wintergard FS-C10-2X self-regulating heating cables and RAYCHEM components to provide a complete solution for frost protection applications.
RAYCHEM SBS Panel: Features & Benefits;
- Switching: up to 12 heat tracing circuits
- Flexible control: Line sensing and / or ambient sensing (PASC)
- Communication: RS485 port for Modbus RTU communication to BMS system
- Simple to design: direct connection of heating cables, no additional junction boxes needed
- Safety: integrated circuit over current and RCD protection
- LED indication: LEDs provide circuit ON (GREEN) status and common FAULT (RED)
- Robust: IP65 sheet steel wall mounted enclosure
- Design: optimal components selected for freeze protection system
- TECHNICAL DETAILS
SPECIFICATIONS Application Pipe freeze protection nVent RAYCHEM XL-Trace, FS-C10-2X trace heating cable Area of Use Ordinary area, indoors Switch accuracy ± 1 K at 5°C (calibration point) Exposure temperature range 10°C to +35°C ambient Electrical Panel Option 3 Way 6 Way 9 Way 12 Way Maximum number of heating circuits 3 6 9 12 Main Incomer A 32 40 63 80 Quantity of contactors 1 2 3 4 Maximum power output kW 11 22 33 44 Supply voltage 3 phase 400/230 V a.c. with N and PE Terminals Heating cable: 3 x 10 mm²
Sensor: 2 x 1.5 mm²Circuit breaker 1 x 16 A (C-type characteristic), per trace heating circuit RCD 30 mA Alarm 1 potential free contact in panel; 1 alarm LED in the door BMS enabled YES ✓ USB port YES ✓ Display and programming Screen type Touch screen, size 4.3" LED indication (GREEN) - power ON
Selectable set temperatures 0°C to +80°C line sensing (standard)
0°C to +30°C ambient sensing (standard)Parameters LINE and or AMBIENT sensing operation modes
HIGH temperature alarm (up to +80°C , OFF)
LOW temperature alarm (-40°C to +75°C, OFF)
Sensor open circuit
Sensor short circuit
Each parameter input and event stored in non volatile memoryCommunication (Elexant 450c) Communication port RS485 Type 2 wire RS485 Cable One shield twisted pair (not included) Length up to 1,200 m Quantity up to 247 devices per port Data rate 2400, 4800, 9600, 19200 baud Parity None, even, odd Stop bits 1, 2 Protocol Modbus RTU Enclosure Material Sheet steel, textured paint, RAL 7035, light gray Ingress protection IP65 Mounting option Wall mounted Entries Bottom face (gland plate) Sensor Type NTC 2 KOhm / 25°C; 2 wire Tip dimensions ⌀ 5mm; length 20 mm Cable length 10 m (standard); extendable up to 150 m using 2 x 1.5 mm² cable Temperature range -40°C to +80°C Optional accessories Additional sensor NTC sensor, 10 m (line sensing) NTC sensor, ambient sensing - APPROVALS
APPROVALS CE, ROHS, WEEE EMC EN 61000-6-1:2007; EN 61000-6-3.2007+A1:2011 - DIMENSIONS
Dimension and Weights Panel Option 3 Way 6 Way 9 Way 12 Way Width mm 400 600 800 800 Height mm 600 600 800 800 Depth mm 210 210 210 210 Weight kg 20 kg 32 kg 54 kg 56 kg - DOWNLOAD DOCUMENTS