Product details
The chemelex® Raychem SBS-HV-ECO control panel, combines with all HWAT-L, HWAT-M and HWAT-R self-regulating heating cables and Raychem components to provide a complete solution for hot water temperature maintenance applications.
Features & Benefits
- Switching: up to 9 heat tracing circuits
- Control: HWAT-ECO v5 smart controller pre-installed
- Ease of installation: direct connection of heating cables, ready to connect power cable
- Safety: integrated circuit over current and RCD protection
- Robust: IP 65 sheet steel wall mounted enclosure
- Design: optimal components selected for hot water temperature maintenance system
- TECHNICAL DETAILS
SPECIFICATIONS Application Hot water temperature maintenance for chemelex® Raychem HWAT-L, HWAT-M and HWAT-R heating cables Area of Use Ordinary area, indoors Switch accuracy ± 1 K at 5°C (calibration point) Exposure temperature range 10°C to +35°C ambient Electrical Panel Option 3 Way 6 Way 9 Way Maximum number of heating circuits 3 6 9 Main Incomer A 32 63 63 Quantity of contactors 1 2 3 Supply voltage 400 VAC 3 phase, N and PE Terminals Heating cable: 3 x 10 mm²
Sensor: 2 x 1.5 mm²Circuit breaker 20 A (C-type characteristic), per heating circuit RCD 30 mA Alarm 1 potential free contact in panel; alarm light indicator on panel front Display and programming (HWAT-ECO) Screen type Touch screen, size 5" LED indication (GREEN) - LED green; power ON
- LED blinking: error warning message
Selectable set temperatures 37°C to +65°C in 24 blocks of 1 hour per day
0°C to +30°C ambient sensing (standard)Selectable operating modes OFF/ ECONOMY / MAINTAIN / HEAT UP Default timer programmes 7 built-in building programmes, customizable in 1 hour intervals Monitoring Boiler temperature HIGH temperature: adjustable range up to 65°C, OFF)
LOW temperature: adjustable range up to 37°C, OFF)Pipe temperature alarm HIGH temperature: adjustable range up to 65°C, OFF)
LOW temperature: adjustable range up to 37°C, OFF)Sensor alarm Sensor: OPEN circuit
Sensor: SHORT circuitHeating cable alarm Cable: OPEN circuit Enclosure Material Sheet steel, textured paint, RAL 7035, light gray Ingress protection IP 65 Mounting option Wall mounted Entries Bottom face (gland plate) Sensor Type NTC 2 KOhm / 25°C; 2 wire Tip dimensions ⌀ 5mm; length 20 mm Cable length 3 m (standard); extendable up to 100 m using 2 x 1.5 mm² cable Temperature range 0°C to +90°C Optional accessories Additional sensor SENSOR-NTC-10M sensor, 10 m (line sensing) Power bank R-PB-POWERSMART for pre-setup in power-off mode of HWAT-ECO v5 - APPROVALS
APPROVALS CE, UKCA EMC EN 61000-6-1:2007; EN 61000-6-3.2007+A1:2011 - DIMENSIONS
DIMENSIONS AND WEIGHT 3 Way 6 Way 9 Way Width 400 mm 600 mm 600 mm Height 600 mm 600 mm 600 mm Depth 210 mm 210 mm 210 mm Weight 45 kg 45 kg 55 kg - DOWNLOAD DOCUMENTS