Trace heating control panel for gutter freeze prevention. The chemelex® Raychem SBS-EV-10 control panel, combines with all GM-2X and GM-2XT self-regulating heating cables and Raychem components to provide a complete solution for gutter and drainpipe freeze protection applications.

Features & Benefits

  • Switching: up to 12 trace heating circuits
  • Flexible control: Moisture and ambient sensing 
  • Control: Raychem EMDR-10 Smart control device
  • Simple to design: direct connection of heating cables, no additional junction boxes needed
  • Safety: integrated circuit over current and RCD protection
  • LED indication: LEDs provide circuit ON (GREEN) status and common FAULT (RED)
  • Robust: IP65 sheet steel wall mounted enclosure
  • Design: optimal components selected for freeze protection system
  • TECHNICAL DETAILS
    SPECIFICATIONS
    ApplicationGutter and drainpipe freeze prevention

    for chemelex® Raychem GM-2X and GM-2XT
    Area of UseOrdinary area, indoors
    Exposure temperature range10°C to +35°C ambient
    Electrical
    Panel Option3 Way6 Way9 Way12 Way
    Maximum number of heating circuits36912
    Main Incomer A326363100
    Quantity of contactors1234
    Supply voltage400 VAC 3 phase, N and PE
    Heating circuit supply voltage230 VAC 50/60 Hz
    TerminalsHeating cable: 3 x 10 mm²
    Sensor: 2 x 1.5 
    mm²
    Circuit breaker1 x 20 A (C-type characteristic), per heating circuit
    RCD30 mA
    Alarm1 potential free contact in panel; 1 alarm LED in the door
    EMDR-10 Control and Monitoring
    Screen typeTouch screen, size 4.3"
    LED indication (GREEN)
    1. power ON
    2. temperature set point YELLOW
    3. moisture sensitivity YELLOW
    4. heating circuit on RED
    Temperature set points-3°C to +6°C:  factory default +2°C 
    Lower temperature limit range-25°C to -5°C:  factory default -15°C
    Operating differential± 0.5 K
    Measuring accuracy± 1.5 K
    Moisture sensitivity range1 (max.) to 10 (min.):  factory default 5
    Post heating time60 minutes energy saving, selectable: (only in temperature range < +1.5°C)
    Enclosure
    MaterialSheet steel, textured paint, RAL 7035, light gray
    Ingress protectionIP65
    Mounting optionWall mounted
    Entries
    Bottom face (gland plate)
    Sensor - Moisture
    TypePTC  3 wire
    Sensor650 mm flat cable
    Cable length4 m (standard); extendable up to 100 m using  3 x 1.5 mm² cable
    Supply voltage230 VAC ±10 %
    Ambient temperature range-30°C  to +65°C continuous
    Sensor - Ambient
    TypePTC
    Enclosure dimensions52 mm wide
    50 mm high
    35 mm depth
    Ingress protectionIP54
    Terminals 1.5 to 2.5 mm² 
    Cable2 x 1.5 mm², max. length 100 m (not included)
    FixingWall mountable


  • APPROVALS
    APPROVALS
    CEIEC 61439


  • DIMENSIONS
    DIMENSIONS AND WEIGHT
    Number of heating circuits36912
    Width  mm400600600600
    Height  mm600600600800
    Depth  mm210210210210
    Weight  kg`32454590