Product details

The nVent RAYCHEM SBS-R-FP control panel, combines with all RAYCHEM self-regulating heating cables and RAYCHEM components to provide a complete solution for frost protection applications.

RAYCHEM SBS Panel: Features & Benefits

  • Switching: up to 6 heat tracing circuits
  • Efficient control: line sensing thermostat for precise control 
  • Control: RAYCHEM Control-11-DIN control device
  • Simple to design: direct connection of heating cables, no additional junction boxes needed
  • Safety: integrated circuit over current and RCD protection
  • Versatile: IP 65 plastic wall mounted enclosure
  • Design: optimal components selected for freeze protection system
  • TECHNICAL DETAILS
    SPECIFICATIONS
    Applicationfrost protection

    for nVent RAYCHEM XL-Trace, FroStop Black, Wintergard FS-C10-2X and ETL-A self regulating heating cables
    Area of UseOrdinary area, indoors
    Exposure temperature range5°C to +35°C ambient
    Electrical
    Panel Option1 Way
    3 Way
    6 Way
    Maximum number of heating circuits136
    Main Incomer A404040
    Quantity of contactors111
    Supply voltage230 VAC
    400 VAC 3 phase, N and PE
    400 VAC 3 phase, N and PE
    Heating circuit supply voltage230 VAC 50/60 Hz
    TerminalsHeating cable: 3 x 10 mm²
    Sensor: 2 x 1.5 
    mm²
    Circuit breaker10 A, 13 A or 16 A (C-type characteristic), per heating circuit
    RCD30 mA
    Alarm1 potential free contact in panel
    Control and Monitoring (Control-11-DIN)
    Screen typeLED colour RED, 12.7mm
    Temperature set points0°C to +63°C
    Lower temperature limit range0°C to 63°C
    Hysteresis± 1 K
    Measuring accuracy± 1 K, ± 2 digits (0..50°C)
    Enclosure
    MaterialPlastic, light gray
    Ingress protectionIP 65
    Mounting optionWall mounted
    Entries
    Bottom face (metric breakaway entries)
    Sensor
    TypePt100  3 wire
    Tip dimensions⌀ 5mm; length 20 mm
    Cable length10 m,  2 x 1.5 mm² cable
    Exposure range0°C  to +70°C
    Accuracy± 1 K
  • APPROVALS
    APPROVALS
    CEIEC 61439-1


  • DIMENSIONS
    DIMENSIONS AND WEIGHT
    Number of heating circuits1 Way3 Way6 Way
    Width  mm418418418
    Height  mm286436586
    Depth  mm148148148
    Weight  kg47.48.8