Product details
nVent RAYCHEM GL-xx are a range of cable glands for use with various size armoured or non-armoured power cables. The glands are available in different sizes and materials and are approved for use in hazardous areas
- TECHNICAL DETAILS
GL series brass nickel plated Ex d IIC Glands nVent RAYCHEM component GL-33, 3/4" NPT Raystat EX-02 thermostat GL-34, 3/4" NPT Raystat EX-02 thermostat (non-armoured cable) GL-38-M25-METAL, M25 JBM-100, JBS-100, JBU-100, JB-EX junction boxes earth plate variants GL series, polyamide (Ex e II) - for use with non-armoured power cable Gland nVent RAYCHEM component GL-36-M25 JBM-100, JBS-100, JBU-100 junction boxes (cable ⌀8 to 17.5 mm) and temperature range -20°C to +75°C GL-45-M32 JB-EX-21, JB-EX-32**, JB-MB-25**, JB-MB-26** (cable ⌀12 to 21 mm) GL-51-M40 JB-Ex-42, JB-EX/21**, JB-Ex-32/**, JB-EX-25/** (cable ⌀17 to 28 mm) GL-55-M25 JB-EX-20, JBM-100, JB-MB-25**, JB-MB-26**, JBS-100, JBU-100 (cable ⌀8 to 15 mm) and temperature range -55°C to +70°C * IMPORTANT* The above numbers are for circuit length estimation only. For more detailed information please request nVent RAYCHEM TraceCalc software design. nVent requires the use of a 30 mA residual current device to provide maximum safety and protection from fire. Where design results in higher leakage current, the preferred trip level for adjustable devices is 30 mA above any inherent capacitive leakage characteristic of the heater as specified by the trace heater supplier or alternatively, the next common available trip level for non adjustable devices, with a maximum of 300 mA. All safety aspects need to be proven - DOWNLOAD DOCUMENTS