Product details
RAYCHEM RAYSTAT V5 electronic controller provides control of self-regulating heating cables for freeze protection and temperature maintenance applications. It is designed for operation with RAYCHEM XL-Trace, FS and ETL heating cables. The current and set point temperatures are displayed via the LED panel and 5 LEDs indicators provide power, temperature and communication status. With an IP65 enclosure the RAYSTAT V5 is suitable for outdoor locations.
RAYSTAT V5: Features & Benefits
- Flexible control: Line sensing and/or ambient sensing (PASC)
- Adjustable range: 0°C to +90°C (line sensing) and 0°C to +30°C (ambient sensing)
- LED indication: 5 LEDs provide status indication
- Simple to design: direct connection of heating cables possible
- USB port: offsite configuration, firmware upgrades
- Communication: relay signals power, temperature or communication status
- Switching: SPDT, 25A, 230 Vac
- TECHNICAL DETAILS
SPECIFICATIONS Application Pipe freeze protection and temperature maintenance for nVent RAYCHEM XL-Trace, FS-C10-2X, Frostop Black and ETL heating cables Area of Use Ordinary area, outdoors Switch accuracy ± 1 K at 5°C (calibration point) Adjustable temperature range -5°C to +15°C Electrical Supply voltage 180 to 253 Vac 50/60 Hz Terminals Power supply: 3 x 6 mm²
Heating cable: 3 x 6 mm²
Alarm: 3 x 1.5 mm²
Sensor: 3 x 1.5 mm²Alarm relay Single pole double throw (SPDT); volt free Switching capacity output relay 25 A 230 Vac Maximum switching capacity (resistive load only) 1 A Vdc, 0.5 A 125 Vac. max. 60 Vdc/ 125 Vac Circuit breaker Max. 20 A (C-type characteristic) Keylock Password protection USB port Pre-installation set-up in power off mode; firmware upgrade Display and programming Screen type LED LED indication (GREEN) - power ON
- heating cable ON
- line sensor CONNECTED
- ambient sensor CONNECTED
- alarm/error INFO
Selectable set temperatures 0°C to +90°C line sensing (standard)
0°C to +30°C ambient sensing (standard)
+91°C to 180°C (module SM-PT-100-1 and PT-100 sensor HARD-78 required)Parameters LINE / AMBIENT sensing operation modes
HIGH temperature alarm (+2°C to +90°C , OFF)
LOW temperature alarm (-40°C to +65°C, OFF)
HYSTERESISEnclosure Material Polycarbonate Ingress protection IP65 Mounting option On wall: mountable DIN rail 35 mm Entries 1 x M25: power supply cable ( ⌀ 11-17mm)
1 x M25: heating cable ( ⌀ 11-17mm)
1 x M20: sensor cableStorage temperature -40°C to +50°C Flammability class DIN EN 60730 / VDE 0631-1 Sensor Type NTC 2 KOhm / 25°C; 2 wire Tip dimensions ⌀ 5mm; length 20 mm Cable length 5 m (standard); extendable up to 150 m using 2 x 1.5 mm² cable Temperature range -40°C to +90°C
+90°C to 180°C (module SM-PT-100-1 and PT-100 sensor HARD-78 required)Optional accessories Additional sensor NTC sensor Sensor module SM-PT-100-1 (required for HARD-78 sensor) PT-100 sensor HARD-78 (exposure temperatures +91°C to +180°C) Powerbank Powerbank *** RAYSTAT V5 accessories may also be ordered separately *** - APPROVALS
APPROVALS CE, ROHS, WEEE EMC EN 61000-6-1:2007; EN 61000-6-3.2007+A1:2011 - DIMENSIONS
DIMENSIONS AND WEIGHT Width 210 mm (excluding glands) Height 90 mm (excluding glands) Depth 85 mm Weight 0.99 kg - DOWNLOAD DOCUMENTS