Product details
The nVent RAYCHEM Elexant 4010i electronic heat tracing control unit. Elexant 4010i Series is a range of compact, full featured, touch screen based, single point heat tracing controllers, with ground fault protection. It provides control and monitoring for both freeze protection and process temperature maintenance. Available with either an electromechanical relay (EMR) for use in non hazardous areas, or solid state relay (SSR) for use in both non hazardous and ATEX/ IECEx Zone 2, Class I Div. 2 Zone 2 hazardous locations. Capable of controlling up to 32A at 277 V a.c.
Available in 4 variants:
- Elexant 4010i-EMR-IS-FW (FRP enclosure - non hazardous locations only)
- Elexant 4010i-EMR-IS-SW (Stainless steel enclosure - non hazardous locations only)
- Elexant 4010i-SSR-IS-FW (FRP enclosure - hazardous areas ATEX/IECEx Zone 2)
- Elexant 4010i-SSR-IS-SW (Stainless steel enclosure - hazardous areas ATEX/IECEx Zone 2)
(All variants fitted with 25 cm x 20 cm window as standard)
Features & Benefits
- ready to install, program and operate
- control up to 32A, 230V a.c.
- measures temperature of up to three directly connection sensors
- line sensing, ambient sensing and proportional ambient sensing control (PASC) capabilities
- equipped with RS485 and Ethernet ports, support both MODBUS/RTU and MODBUS /TCP protocols
- TECHNICAL DETAILS
SPECIFICATIONS Application pipe freeze protection and temperature maintenance Area of Use non-hazardous area
hazardous areas Zone 2Exposure temperature range -40°C to +60°C Storage temperature range -55°C to +85°C Supply voltage 110 V a.c. to 254 V a.c. ±10% 50/60 Hz Power consumption < 24W Electromagnetic compatibility IEC 61326-1:2012 / EN 61326-1:2013 Control Relay type double-pole, mechanical (EMR variants)
double-pole, solid-state (SSR variants)Maximum voltage 277 V a.c. 50/60 Hz Maximum current 32A @ 40°C, de-rated to 24A @ 50°C and further de-rated to 16A @ 60°C (EMR variants)
32A @ 40°C, de-rated to 24A @ 50°C and further de-rated to 16A @ 60°C (SSR variants)Control algorithms On/Off, PASC, always on, always off (EMR variants)
On/Off, proportional, PASC, always on, always off (SSR variants)Control range -200°C to 700°C Monitoring Temperature LOW alarm range: -200°C to 700°C
HIGH alarm range: -200°C to 700°CGround fault Alarm range: 10 mA to 500 mA or OFF
Trip range: 10 mA to 500 mA or OFFCurrent LOW alarm range: 0.1 A to 100 A or OFF
HIGH alarm range: 0.1 A to 100 A or OFF
Power limit range: 8 W to 30 kWVoltage LOW alarm range: 80 V a.c. to 300 V a.c. or OFF
HIGH alarm range: 80 V a.c. to 300 V a.c. or OFFResistance LOW resistance range: 1% to 100% of deviation from nominal
HIGH resistance range: 1% to 250% of deviation from nominalAutocycle 1 to 750 hours Temperature Sensor Inputs Qty 3. Each can be individually set to one of the types below; 100Ω platinum RTD 3-wire, α=0.00385 ohms/ohm/°C
-200°C to 700°C (-328°F to 1292°F), ± 1°C
can be extended with a 3-conductor shielded cable of 20Ω maximum per conductor100Ω nickel iron RTD 2-wire, α=0.00599 ohms/ohm/°C
-73°C to 350°C (-99°F to 662°F), ± 1°C
can be extended with a 2-conductor shielded cable of 20Ω maximum per conductor100Ω nickel RTD 2-wire, α=0.00618 ohms/ohm/°C
-70°C to 250°C (-94°F to 482°F), ± 1°C
can be extended with a 2-conductor shielded cable of 20Ω maximum per conductorThermocouple Require external 4-20 mA converter
4-20 mA current loop, ± 0.05 mA, 24 V d.c. loop powerThe Elexant 4010i-IS variants are equipped with intrinsic safety barriers at the RTD inputs. RTD intrinsic safety associated apparatus entity parameters: Uo (maximum output voltage): 5.4 V
Io (maximum output current): 0.83 mA
Po (maximum output power): 0.449 W
La (maximum external inductance): 2 mH
Ca (maximum external capacitance): 65 uFDigital Inputs Quantity two multi-purpose inputs for connection to external dry (voltage free) contact or DC voltage
can be configured for Hand-Off-Auto (HOA) operationRating 100 Ω max loop resistance or 5-24 V d.c. @ 1mA maximum Outputs Alarm relay Form-C dry contact: 00 V a.c. to 277 V a.c. 3A 50/60Hz
can be configured for Hand-Off-Auto (HOA) operationAuxiliary 24 V d.c. max load of 250 mA @ 40°C, de-rated to 165 mA @ 60°C Configuration / programming Method touch screen display Units °C or °F Idle display sensor temperature, control temperature, heater current, voltage, power, alarm status LEDs status: heater on, alarm conditions, receive / transmit data Memory non-volatile, restored after power loss, checksum data checking Stored usage parameters minimum and maximum process temperature
maximum ground fault current
minimum and maximum voltage
maximum heater current
power accumulator
contactor cycle count
total time in use
heater on timeAlarm conditions low / high temperature
low / high current
low / high voltage
low / high resistance
ground-fault alarm / trip
RTD failure
loss of programmed values
EMR or SSR failure
equipment protection trip
attached device alarm
contactor lifetime exceededAlarm modes normal (solid on), flash (on & off), toggle (re-ring new alarms) Control algorithms *-EMR variants: On/Off, PASC, always on, always off
*-SSR variants: On/Off, proportional, PASC, always on, always offEquipment protection ground fault trip, low / high temperature limit, Soft-Start features, (heat trace output limiting, SSR overcurrent protection, circuit breaker nuisance trip prevention) Load shedding Up to 8 zones, with temperature fail safe and communication timeout (requires nVent RAYCHEM Supervisor) Profiles Built-in default setting profiles for common heat trace applications. Up to two additional user configurations can be saved and reloaded. Saved configurations can be saved to and loaded from a USB thumb drive Network Automatic network configuration with DHCP, or static IP configuration Firmware updates User via USB thumb drive Multi language interface English, French, German, Spanish, Russian Other Password protection, text tags / identifiers for controller and temperature sensors Communication Communication port RS-485 and Bluetooth Class 1 Type 2-wire RS-485 Cable One shielded twisted pair (not included) Length up to 1,200 m (4000 ft) maximum Quantity up to 247 devices per port Data rate 9600, 19200, 38400, 57600 baud Parity None, even, odd Stop bits 0, 1, 2 Protocol Modbus RTU Enclosure Material *-FW variants: Fibre reinforced plastic (FRP)
*-SW variants: Stainless steel (SS304)Ingress protection *-FW variants: IP 64 (FRP enclosure)
*-SW variants: IP 66 (stainless steel enclosure)Entries 2 x M25 - power
2 x M20 - digital communication
3 x M16 - temperatures sensorsSurface mounting 4 x M8 mounting holes
Elexant-4010i-EMR-IS-FW variant: 152 mm x 278 mm centres
Elexant-4010i-EMR-IS-SW variant: 152 mm x 279 mm centres
Elexant-4010i-SSR-IS-FW variant: 143 mm x 279 mm centres
Elexant-4010i-SSR-IS-SW variant: 143 mm x 279 mm centresConnection terminals Power supply input screw terminals: 0.2 mm2 to 16.8mm2 Heat cable output screw terminals: 0.2 mm2 to 16.8mm2 Torque range 1.2 - 1.5 Nm Ground (earth) three box lugs 2.0 mm2 to 33.6 mm2 Sensor / Other terminals Cage clamp terminals 0.08 mm2 to 3.3 mm2 - APPROVALS
APPROVALS ATEX: DEMKO 18ATEX2091X
II 3 (1) G Ex ec nc [ia Ga] IIC Ta Gc
IP64 (FW) IP66 (SW)IECEx: UL 18.0098X
II 3 (1) G Ex ec nc [ia Ga] IIC Ta Gc IP64 (FW) IP66 (SW) - DIMENSIONS
DIMENSIONS (mm) AND WEIGHT (kg) Elexant variant 4010i-EMR-IS-FW 4010i-EMR-IS-SW 4010i-SSR-IS-FW 4010i-SSR-IS-SW Width 226 231 226 231 Height 305 300 308 308 Depth 156 160 184 191 Weight 4.6 6.6 6.6 8.6 Mounting holes 4 x M8 4 x M8 4 x M8 4 x M8 Mounting centres 152 x 278 143 x 279 152 x 279 143 x 279 - DOWNLOAD DOCUMENTS